The
120Vac and 240Vac Coil-Lock products shown in the above
photo represent a major breakthrough in assembling electronic
components for cost-effective voltage sag protection.
The Coil-Lock electronics works with ac relays, contactors
and solenoids as a hold-in-device that keeps motors
and other critical process elements on line during those
annoying momentary voltage sags. Literally any device
that is controlled by energizing an ac coil, when powered
through a Coil-Lock unit will continue to operate as
intended through these power disturbances. Not only
does the Coil-Lock protect the coil circuits from voltage
sags, but also has the ability to protect coils from
lightning and switching induced transients just like
a surge suppressor.
The
Coil-Lock's compact packaging combined with its Din
Rail octal relay socket-mounting base make the Coil-Lock
unit easy to fit into almost any commercial and industrial
application. Electric service supply voltage sags and
dips are a fact of life. Caused by weather, falling
tree limbs, and animal intrusion events, electric utility
system faults are unavoidable and can be expected dozens
of times a year at the typical facility site. The good
news is that critical process equipment can stay up
and running when you need it by applying PQSI Coil-Locks
on relays, contactors, and motor starters that often
are diagnosed as weak links in automated production
lines because these coil operated devices usually have
a low tolerance to electric service voltage sags.
The
following figure depicts the enhanced voltage sag protection
provided by the Coil-Lock product. The figure shows
the typical unprotected relay or contactor's capability
to ride through voltage sags down by 15% from its nominally
rated voltage (yellow area in the figure). The same
relay or contactor, when protected by the Coil-Lock,
will continue to keep operating with voltages sags down
by 75% from its nominally rated voltage (green area
in the figure). For voltage sags down by greater than
75%, the Coil-Lock de-energizers the relay or contactor
coil to maintain the safety function for emergency stop
circuits (red area in the figure).

For
more information click on the buttons below
FOR
TECHNICAL INFORMATION AND PRICING, CONTACT:

Power
Quality Solutions Inc.
12529
Coral Reef Circle
Knoxville, TN 37922-5490
Phone:
865-671-8364
Global Fax: 800-881-2893
Alternate Fax: 702-973-7970